SEDM-L – Multi compartment smoke extraction damper allows usage in smoke extraction ducting systems. Suitable for heat and smoke extraction from several comparements at the same time.
Characteristics
- Square multi-blade fire damper from 200 × 430 mm to 1 200 x 2 030 mm
 - CE certified acc. to EN 12101-8
 - Construction length only 250 mm
 - Tested in accordance with EN 1366-10
 - Classified acc. to EN 13501-4+A1 as EIS 120, actuating AA/MA for multi Fire Compartment
 - Cmod classification, cycling test C 10000 acc. to EN 12101-8
 - External Casig leakage class C,
 - Internal leakage class 3 acc. to EN 1751
 - Damper actuating by electrical actuator
 - Max. air speed in the system of 12 m/s, allowed pressure up to 500Pa, or underpressure up to -1000 Pa