Recair ventilation units can be equipped with multiple control options:
No electric controls – The machine delivery does not include controllers, electrical panels, automation components (temperature sensors, differential pressure transmitters, etc.) or their cabling. There is no pre-installed electrical panel enclosure on the machine.
No controls + BAS installation surface – It is possible to select mounting surfaces for Building Automation Systems (BAS) installations on the machines. In practice, this means 100-150mm blind spots pre-selected at specific points for the installation of sensors and transmitters. Mounting surfaces significantly simplify and expedite BAS installations when performed on-site. At the same time, these mounting surfaces slightly extend the overall length of the machine.
Terminal block connections – The machine is equipped with a panel. All control circuits of the devices included in the machine delivery, which have been installed on the machine, are cabled to the panel’s terminal blocks. For example, fans, rotor controllers, etc.
Terminal block unit + BAS components – The equipment includes the terminal block panel setup. Additionally, BAS components are installed on the machine, which are cabled and connected to the machine panel’s terminal blocks. The equipment does not include programming.
Electrical cabinet – The machine is equipped with an electrical panel that contains the necessary power supply components for the machine’s electrical devices, such as circuit protectors and motor protection switches. Fans and other electrical devices included in the machine delivery and installed on the machine are cabled and connected to the machine’s electrical panel at the factory. The machine delivery does not include the air handling unit controller, automation components, or their cabling and connections.
Electrical cabinet unit + BAS components – The equipment includes the electrical panel machine setup. In addition, BAS components are installed on the machine, which are cabled and connected to the machine’s electrical panel’s terminal blocks. The equipment setup does not include programming.
Electr. And control panel (Ouflex) – The machine equipped with an electrical and control equipment panel includes automation components to be installed in the air handling unit, already cabled and connected, the electrical panel, and a pre-programmed controller. The machine’s automation functionality has been tested at the factory. Ouflex unit come as standard with Modbus RTU and Modbus TCP / IP.